High Frequency Double Conversion True Online Pure Sinewave UPS Systems |
|
|
Home | Products | Email | Contact Details | Profile | Lightning Information Tel: (++27) 11 886-7874 Fax : (++27) 11 787-0178 | ||
The DP1000
The DP1000 uses micro processor control, to recreate the perfect sine wave for your loads. The pulse inverter will protect the UPS's Loads from all types of mains conditions that will damage critical loads. THE DP1000 is supplied standard with a thyristor static bypass switch and manual bypass. The DP1000 is fitted standard with a front panel mimic. An optional LCD display can be fitted. The DP1000 can be fitted with a potential free contact card for BMS interface or remote status monitoring.
Features include :
Home | Full Product List | EMail | Our Contact Details
Copyright © 2005 Sinetech c.c. All rights reserved.
Print Version (99kb)
DP1000 SERIES
High Frequency Online Double Conversion Sinewave4KVA - 10KVA
Single Phase

FRONT VIEW
REAR VIEW
MODEL
DP1004-11
DP1005-11
DP1006-11
DP1008-11
DP1010-11
Output
Phase
1 phase, 2 wire + earth, 0,8 lag pf rated, sinewave
VA Rating
4KVA
5KVA
6KVA
8KVA
10KVA
KW Rating
3,2KW
4KW
4,8KW
6,4KW
8KW
Output current at rated VA load
18A
23A
28A
36A
45A
Voltage
220/230VAC - Other voltages on request
Static Regulation
±1%
Dynamic Regulation
±5% (100% load step) Recovery to 2% within 20ms)
Frequency : Free Running
Synch to Mains
50Hz ± 0.01%
48.5 - 51.5Hz adjustable, other frequencies on request
Total Harmonic Distortion
< 3% for linear loads, < 5% for non linear loads
Overload Capacity
105% continuous / 110% 60 min. / 125% 1 min. / 150% 25 sec.
Crest Factor
> 3:1 @ rated inverter load
Efficiency AC-AC
90% @ full load and rated voltage
Efficiency inverter
92% @ full load
Output transformer
Double wound for galvanic isolation
Output protection
Electronic and circuit breaker/fuses
Input
Voltage
220/230VAC 1 Phase
2 Wire + E, other voltages on request
Frequency
50/60Hz ± %5, other frequencies on request
Voltage Range
220 volts -10% to +15% before going onto battery
DC Link and Battery
Voltage
Nominal voltage 192V, Float charge 216V,
Shutdown voltage 157V, all voltages adjustable on the machine
Maximum DC charge current
8 amps adjustable
Ripple Voltage
Less than 1%
Internal Batteries 12V/7Ah
Yes
No
Internal Batteries 12V/12Ah
Yes
No
Battery types available
3-5yr low maintenance, 3-5 and 10yr VRLA, all types of vented lead acid and nickel cadmium
Number of lead acid cells
96 cells
Oscillator
Crystal
Internal to microprocessor
Static Bypass Switch
Type
Thyristor bridge
Rated Current
1.5 In
Overload Capacity
150% Continuous 200% 1 Min. 1000% 10ms.
Environmental
Temperature
0 - 40 deg. Celsius, 15 - 25 deg. recommended, 0 - 35 deg. continuous
Humidity
0 - 90% non condensing
Maxium altitude without derating
0 - 2000 meters
Cabinet colour
RAL7032 interior
Heat generation at full load
520 watts
650 watts
780 watts
1040 watts
1300 watts
Recommended supply CB
30A 1P
30A 1P
45A 1P
63A 1P
63A 1P
Dimensions
UPS (w x h x d)
Battery box type 1P
Battery box type 3P
350 x 860 x 760mm
350 x 860 x 760mm
540 x 930 x 760mm
Noise Level
dBA
< 50
Optional Items
RS232, GSM, LCD display, Voltage free contacts, Shutdown and monitoring software
Other
Degree of protection
IP21
Warranty
12 months
![]()