High Frequency Double Conversion True Online Pure Sinewave UPS Systems |
|
|
Home | Products | Email | Contact Details | Profile | Lightning Information Tel: (++27) 11 886-7874 Fax : (++27) 11 787-0178 | ||
The DP2000
The DP2000 is supplied standard for a single input configuration. It is however possible to increase power reliability by installing the DP2000 with a split bypass configuration. To further improve redundancy a hot stand-by configuration can be used whereby one UPS backs up another UPS.
THE DP2000 is supplied standard with a single phase thyristor static bypass switch and a manual bypass. The DP2000 can be supplied with an isolation transformer in a separate cabinet.The DP 2000 is fitted standard with a front panel mimic. An optional LCD display can be fitted. The front panel mimic gives real time status at a glance, while the LCD display allows diagnostics of the UPS. The DP2000 can be fitted with a potential free contact card for BMS interface or remote status monitoring.
Features include :
Home | Full Product List | EMail | Our Contact Details
Copyright © 2005 Sinetech c.c. All rights reserved.
Print Version (106kb)
DP2000 SERIES
High Frequency Online Double Conversion Sinewave10KVA - 30KVA
Three Phase In/ Single Phase Out

FRONT VIEW
REAR VIEW
MODEL
DP2010-31
DP2015-31
DP2020-31
DP2025-31
DP2030-31
Output
Phase
1 phase, 2 wire + earth, 0,8 pf rated, sinewave
VA Rating
10KVA
15KVA
20KVA
25KVA
30KVA
KW Rating
8KW
12KW
16KW
20KW
24KW
Output current at rated VA load
45A
68A
91A
111A
133A
Voltage
220/230VAC - Other voltages on request
Static Regulation
±1%
Dynamic Regulation
±5% (100% load step) Recovery to 2% within 20ms)
Frequency : Free Running
Synch to Mains
50Hz ± 0.02%
48.5 - 51.5Hz adjustable, other frequencies on request
Total Harmonic Distortion
< 3% for linear loads, < 5% for non linear loads
Overload Capacity
105% continuous / 110% 60 min. / 125% 1 min. / 150% 25 sec.
Crest Factor
> 3:1 @ rated inverter load
Efficiency AC-AC
90% @ full load and rated voltage
Efficiency inverter
92% @ full load
Output transformer
Double wound for galvanic isolation
Output protection
Electronic and circuit breaker/fuses
Input
Voltage
380/400VAC 3 Phase
4 Wire + E, other voltages on request
Frequency
50/60Hz ± %5, other frequencies on request
Voltage Range
380/400 volts -10% to +15%
DC Link and Battery
Voltage
Nominal voltage 360V, Float charge 405V,
Shutdown voltage 295V, all voltages adjustable on the machine
Maximum DC charge current
10 amps adjustable
Ripple Voltage
Less than 1%
Internal Batteries 12V/7Ah
Yes
No
No
No
No
Internal Batteries 12V/12Ah
Yes
No
No
No
No
Battery types available
3-5yr low maintenance, 3-5 and 10yr VRLA, all types of vented lead acid and nickel cadmium
Number of lead acid cells
180 cells
Oscillator
Crystal
Internal to microprocessor
Static Bypass Switch
Type
Thyristor bridge
Rated Current
1.5 In
Overload Capacity
150% Continuous 200% 1 Min. 1000% 10ms.
Environmental
Temperature
0 - 40 deg. Celsius, 15 - 25 deg. recommended, 0 - 35 deg. continuous
Humidity
0 - 90% non condensing
Maxium altitude without derating
0 - 2000 meters
Cabinet colour
RAL7032 interior
Heat generation at full load
1100 watts
1650 watts
2200 watts
2500 watts
3000 watts
Recommended supply CB
60A 3P
80A 3P
100A 3P
125A 3P
160A 3P
Recommended supply cable for bypass and rectifier from 1 feeder
10mm2
4W + E
16mm2
4W + E
25mm2
4W + E
25mm2
4W + E
35mm2
4W + E
Recommended output CB
60A 1P
80A 1P
100A 1P
125A 1P
160A 1P
Recommended supply cable for bypass and rectifier from 1 feeder
10mm2
2W + E
16mm2
2W + E
25mm2
2W + E
25mm2
2W + E
35mm2
2W + E
Dimensions
UPS (w x h x d)
Battery box type 1P
Battery box type 3P
540 x 930 x 760mm
350 x 860 x 760mm
540 x 930 x 760mm
700 x 800 x 1600mm
Noise Level
dBA
< 55
Optional Items
RS232, GSM, LCD display, Voltage free contacts, Shutdown and monitoring software
Other
Degree of protection
IP21
Split bypass operation
Yes
Warranty
12 months
![]()