High Frequency Double Conversion True Online Pure Sinewave UPS Systems |
|
|
Home | Products | Email | Contact Details | Profile | Lightning Information Tel: (++27) 11 886-7874 Fax : (++27) 11 787-0178 | ||
The DP3000
The DP3000 is available with windows based service software allowing interrogation of the UPS. This software gives a detailed service report including an event history.
An option with the DP3000 UPS is for it to be supplied with a battery monitoring system.
The DP3000 uses micro processor control and pulse width modulation (PWM), to recreate the perfect sine wave for your loads. The three phase, IGBT inverter will protect the UPS’s loads from all types of mains conditions that will damage critical loads. The DP3000 is fitted standard with a front panel mimic and LCD display.
Features include :
Home | Full Product List | EMail | Our Contact Details
Copyright © 2005 Sinetech c.c. All rights reserved.
Print Version (110kb)
DP3000 SERIES
High Frequency Online Double Conversion Sinewave10KVA - 60KVA
Three Phase In / Three Phase Out

FRONT VIEW
FRONT DOOR OPEN
MODEL
DP3010-33
DP3015-33
DP3020-33
DP3030-33
DP3040-33
DP3060-33
Output
Phase
Three phase, 4 wire + earth, 0,8 pf rated, sinewave
VA Rating
10KVA
15KVA
20KVA
30KVA
40KVA
60KVA
KW Rating
8KW
12KW
16KW
24KW
32KW
48KW
Output current per phase at rated VA load
14A
21A
29A
43A
58A
87A
Voltage
380/400VAC - Other voltages on request
Static Regulation
±1%
Dynamic Regulation
±5% (100% load step) Recovery to 2% within 20ms)
Frequency : Free Running
Synch to Mains
50Hz ± 0.02%
48.5 - 51.5Hz adjustable, other frequencies on request
Total Harmonic Distortion
< 3% for linear loads, < 5% for non linear loads
Overload Capacity
105% continuous / 110% 60 min. / 125% 1 min. / 150% 25 sec.
Crest Factor
> 3:1 @ rated inverter load
Slew Rate
1Hz per second adjustable
Phase imbalance at full load / 100% unbalanced load
< 1%
Efficiency AC-AC
90% @ full load and rated voltage
Efficiency inverter
92% @ full load
Output transformer
Double wound for galvanic isolation
Output protection
Electronic and circuit breaker
Input
Voltage
380/400VAC 3 Phase
4 Wire + E, other voltages on request
Frequency
50/60Hz ± %5
Voltage Range
380/400 volts -10% to +15%
DC Link and Battery
Voltage
Nominal voltage 360V, Float charge 405V,
Shutdown voltage 295V, all voltages adjustable on the machine
Maximum DC charge current
20 amps adjustable
Ripple Voltage
Less than 1%
Battery types available
3-5yr low maintenance, 3-5 and 10yr VRLA, all types of vented lead acid and nickel cadmium
Number of lead acid cells
180 cells
Oscillator
Crystal
Internal to microprocessor
Static Bypass Switch
Type
Thyristor bridge
Rated Current
1.5 In
Overload Capacity
150% Continuous 200% 1 Min. 1000% 10ms.
LCD display as standard
Measurement of input, bypass and output voltage, output current and frequency, DC voltage and event history
Environmental
Temperature
0 - 40 deg. Celsius, 15 - 25 deg. recommended, 0 - 35 deg. continuous
Humidity
0 - 90% non condensing
Maxium altitude without derating
0 - 2000 meters
Cabinet colour
RAL7032 interior
Heat generation at full load
890 watts
1350 watts
1800 watts
2700 watts
3600 watts
5400 watts
Recommended supply CB
30A 3P
40A 3P
50A 3P
80A 3P
100A 3P
125A 3P
Recommended supply cable for bypass and rectifier from 1 feeder
4mm2
4W + E
6mm2
4W + E
10mm2
4W + E
16mm2
4W + E
25mm2
4W + E
35mm2
4W + E
Recommended output CB
20A 3P
30A 3P
30A 3P
50A 3P
60A 3P
100A 3P
Recommended output cable
2,5mm2
4W + E
4mm2
4W + E
4mm2
4W + E
6mm2
4W + E
16mm2
4W + E
25mm2
4W + E
Dimensions
UPS (w x h x d)
Battery box 33P
Batt 7400
650 x 1600 x 750mm
650 x 1600 x 750mm
(up to 30 x 12V / 102Ah batteries)
Noise Level
dBA
< 65
Optional Items
RS232, GSM, Voltage free contacts, Shutdown and monitoring software, Battery manager, Input harmonic filter
Other
Degree of protection
IP21
Split bypass operation
Yes
Warranty
12 months