Powering the Future |
|
ALL PRODUCTS Solar Panels Solar Design Service PV Solar Systems Charge Controllers Inverters Batteries Battery Chargers Solar Chargers Battery Stands/Cabinets Combiner Boxes Mounting Structures UPS Systems Long Backup Systems Wind Generators Diesel Generators Lightning/Surge Protection Brand Names | LH SERIES UPS SYSTEMS : True Online Double Conversion Intelligent Sinewave Long Backup (no internal batteries) 700VA - 3000VA Click on the pictures below to view full specifications on the UPS system |
![]() |
|||
|
The LH Series UPS is an advanced true on-line, double conversion UPS system which is suitable for larger battery banks to provide longer back-up times. It is Intelligent Microprocessor controlled. Generator compatibility is one important advantage for certain power supply conditions and RS232 communication advanced design make it compatible for sophisticated monitoring software. The 2KVA and 3KVA models have better power security through 'Redundant' features and also have an internal SNMP slot option.
![]()
|
![]() LH UPS |
||||
| TECHNICAL SPECIFICATIONS | |||||
| MODEL |
LH700 |
LH1000 |
LH2000 |
LH3000 |
|
|
Output |
VA Rating |
700VA |
1000VA |
2000VA |
3000VA |
|
Wattage |
450W |
700W |
1400W |
2000W |
|
|
Current (100-120V / 220-240V) max. |
3A |
4.3A |
8.7A |
13A |
|
|
Voltage |
220, 230, 240V +/- 2% |
220, 230, 240V +/- 2% |
|||
|
Frequency |
50 / 60 Hz Auto select |
||||
|
Wave form |
Pure sinewave |
||||
|
Harmonic Distortion |
Less than 3% at full load (Linear load) |
||||
|
Charger Output |
Max. Voltage |
27,5VDC |
41,5VDC |
83VDC |
110VDC |
|
Current (total max.) |
12A |
12A |
8A |
6A |
|
|
Input |
Voltage |
160 V - 275 V |
|||
|
Frequency |
45 - 65 Hz Auto select |
||||
|
Runtime |
Full Load |
as per battery set |
|||
|
Half Load |
as per battery set |
||||
|
Transfer Time |
INV to Bypass / Bypass to INV |
Less than 4 msec. (2 msec. Min) / Zero-Cross Transfer |
|||
|
Power Failure Recovery |
0 msec. to or from battery |
||||
|
Required External Battery Pack |
DC Voltage Nominal |
24 VDC |
36 VDC |
72 VDC |
96 VDC |
|
DC Voltage Float |
27,5 VDC |
41,5 VDC |
83 VDC |
110 VDC |
|
|
Type |
12V / 7AH Lead acid maintenance free |
||||
|
Battery Quantity |
External batteries as required per model | ||||
|
Recharge Time |
5 - 8 hours (depending on size of external battery pack) |
||||
|
Recharge Current |
6 A (max.) |
||||
|
Efficiency |
AC to AC |
85% min. |
|||
|
Audible Noise |
|
< 40 dBA |
< 50 dBA |
||
|
Indicators |
LED Display |
LINE, INV, BAT, BYPASS, FAULT, BAT / LOAD LEVEL |
|||
|
Auto Restart |
|
Yes |
|||
|
DC Start-up |
|
Yes |
|||
|
Protection |
Overload |
> 110% of full load with 15 - 20 sec. Delay, 150% immediately |
|||
|
Over / Undervoltage at I/P. O/P |
Inverter shutdown protection |
||||
|
Phone Jack |
RJ-11/RJ-45 |
||||
|
Short Circuit |
Shut down and won't transfer to bypass output, will work normally again when short circuit is removed |
||||
|
Approved |
EMC/LVD (230 V, 50 Hz) |
EN50091-2 / EN50091-1 |
|||
|
C-TICK (240 V, 50 Hz) |
AS-NZS 3548 |
||||
|
Safety |
TUV GS Mark EN50091-1-1, UL 1778 |
||||
|
USA FCC (120 V, 60 Hz) |
FCC PART 15 |
||||
|
CNS BCIQ (110 V, 60 Hz) |
CNS 13438 |
||||
|
IMMUNITY (120V / 110V / 100V, 50/60 Hz) |
IEEE 587 CLASSA |
||||
|
Computer Interface |
LAN / RS232 Interface |
Mains fail, battery low & remote shutdown UPS, RS232 communication |
|||
|
Mechanical |
Dimensions (W x H x D) (cm) |
14 x 19 x 44 |
14 x 19 x 44 |
19 x 32 x 50 |
19 x 32 x 50 |
|
Weight w/ Battery (kg) N.W / G.W. |
12.3 / 13.8 |
14.8 / 16.3 |
32.4 / 36.4 |
38.2 / 42.2 |
|
|
Environment |
Temperature |
0 deg C to 40 deg C |
|||
|
Humidity |
0 - 95% Non-Condensing |
||||
Copyright © 2011 Sinetech c.c. All rights reserved.