Line Interactive Intelligent Pure Sinewave UPS Systems Long Backup |
|
|
Home | All Products | Service & Repairs | Email | Contact Details | Profile | Lightning Information Tel: (++27) 11 886-7874 Fax : (++27) 11 787-0178 | ||
The LT Series UPS is an advanced true sinewave line-interactive UPS system which is designed to prevent any spike, sags and blackout from reaching your sensitive equipment; ranging from computers and tele-communications systems to computerised instruments. The LT Range has a more powerful battery charger and is therefore suitable for larger battery banks, providing longer back-up times.
Under normal power conditions the UPS filters out all small fluctuations. During power failure, the unit employs its internal maintenance-free batteries to supply back-up power without any interruption. The UPS is equipped with many features, which make both your equipment and UPS more reliable.
LT700 LT1000 LT1500 LT2000
Home | Full Product List | EMail | Our Contact Details
Copyright © 2005 Sinetech c.c. All rights reserved.
Print Version (495kb)
LT SERIES UPS SYSTEM
Intelligent Line Interactive Sinewave - Long backup700 / 1000 / 1500 / 2000VA



MODEL
Output
VA Rating
700VA
1000VA
1500VA
2000VA
Wave form
Pure sinewave
RMS Power
470W
670W
1000W
1200W
Current 230V
3.0A
4.3A
6.5A
8.7A
Voltage regulation
230V + 11.3% / - 15.2% (under line mode)
230V ± 6% (under backup mode)
Frequency regulation
45Hz to 65Hz (under line mode)
50Hz or 60Hz ± 0.Hz (under backup mode)
Efficiency AC to AC
> 95%
Total harmonic distortion
< 5% at full non-linear
< 10% when battery low
Overload capacity
> 110% of full load with 10 sec. delay
> 150% of full load with 1 sec. delay
Input
Phase
Single Phase with ground
Voltage
171VAC-278VAC
Frequency
45 / 65Hz Auto Select
Current Nominal
3.8A
6.1A
7.8A
10.6A
Current Maximum
4.4A
6.9A
9.1A
12.2A
Power Factor
Under full load (p.f.=0.67/0.6) nominal input voltage
Under full load (p.f.=0.67/0.6) low input voltage and max. charging current
Battery
DC Voltage Minimum
20 VDC
30 VDC
40 VDC
50 VDC
DC Voltage Nominal
24 VDC
36 VDC
48 VDC
60 VDC
DC Voltage Maximum
27.5 VDC
41.5 VDC
55 VDC
69 VDC
Type
12V / 7AH Lead acid maintenance free
No of batteries
2 pcs
3 pcs
4 pcs
5 pcs
Full charge voltage
27.5 VDC
41.5 VDC
55 VDC
69 VDC
Charge current
*5.0A - Caution : suggest charging current for more than 28Ah battery capacity
Backup time
Several min. to several hours depending on capacity of external battery
Recharge Time
8 hours dependant on capacity of external battery
Audible Noise
< 45 dBA at one meter
Transfer Switch
Type
Relay
Transfer time
Bypass to inverter, inverter to bypass : 5 ms (typical)
Transfer criteria
Line abnormal
Interface Signal
Signal Type
Photo-coupled LAN signal and isolated RS232
Connector Type
DB9 female connector
Signal
Line failure, low battery
Remote shutdown
UPS can be shutdown by external signal
Remote Control
Programmable shutdown-reboot function and show out UPS status with "RUPS/UPSilon2000" software
Protection
Electronic overload and short circuit protection
Automatic shutdown at low battery voltage
Control
On/Off Switch
Test/Alarm-reset switch
Line input circuit breaker or fuse
Indicators
Status
LINE(G), ON BAT.(Y), ON AVR(Y), BAT. WEAK/LOW BAT.(R), FAULT/OVERLOAD(R)
Load Level
3 Green LEDs and Fault/OVERLOAD (R)
Audible Alarm
Battery discharge
From 10 sec. 2 beeps to 2 sec. 2 beeps to signify battery level
Every sec. 2 beeps when battery low
Overload
Two beeps every second
Fault
Beeps continuously
Cooling
Air convection
Forced air cooling with fan
Mechanical
Dimensions (WxHxD)(mm)
120x160x360
160x200x450
160x200x450
160x200x450
Weight G.W. (kg) No batteries
22.9 / 24.1
13.4 / 14.6
16.9 / 18.1
16.9 / 18.1
Environment
Temperature
00C - 400C
Humidity
0-95% Non-Condensing
Altitude
Less than 3000 meters above sea level
Storage Temperature
- 150C to 400C
Approvals
Safety
CE / TUV, C-Tick
EMC
EN50091-2, CE
LVD
EN50091-1
Optional
SNMP External Card
![]()