Sinetech Uninterruptible Power Supplies and Power Protection Modular 19"Rack Mount
Telecom Sinewave Inverters

Home | Products | Email | Contact Details | Profile | Lightning Information
Tel: (++27) 11 886-7874 Fax : (++27) 11 787-0178

Print Version
TELECOM SERIES
Model RDI 1000VA-48VDC-230VAC
1000VA / 48VDC / 230VAC
2U up to 16 units in parallel

The Telecom Series of design-improved modular inverters can be supplied from any DC source in voltage range from 40 up to 80 VDC, providing pure sine wave output.Several inverters can be connected in parallel to achieve the requested total power, including redundancy for best availability. Thanks to the full DSP control, true redundancy is achieved, while all information is available both locally and remotely with SYS3000 controller and PSM2000 software.The high frequency conversion and the topology used allow very high efficiency to be reached in a compact and user-friendly design. The environmentally friendly range complies with International, European and general Telecoms standards.

Some of the product features include:-

  • 2U up to 16 units in parallel
  • High efficiency
  • Full Digital Signal Processing control
  • Outstanding response time
  • Input/Output Radio Frequency Interference compliant to FCC
  • Complete Supervision possibility
  • Parallel operation in True Redundant System
  • Large DC input voltage range
  • Patented technology
1000VA 48VDC Sinewave Inverter

Model RDI 1000VA-48VDC-230VAC Inverter

TECHNICAL SPECIFICATIONS

Model   120VAC 230VAC
Input Operating voltage range 40 up to 80 VDC
Maximum input current < 28,5 A < 27,7 A
Output specifications Nominal output voltage 120V adjustable (108...125VAC) 230V adjustable (200...240VAC)
Output voltage tolerance ± 3% of adjustable nominal voltage
Output voltage frequency 50Hz or 60Hz selectable
Total harmonic distortion </= 3% (on linear load at nominal power)
Total transient recovery time </= 0,3 msec (typical)
Turn-on-delay < 3 sec.
Nominal value of output current 8.33 A 4.35 A
Crest factor at nominal power 3
Output power Nominal value 1000 VA 1000 VA
Overload (± 15%, 5 sec. max. self protected) 2000 VA 2000 VA
Permanent overload 120% 120%
Power factor for 100% power 0 Inductive to 0 capacitive
Full 4 quadrants operation
Electro-magnetic compatibility Standards applied for immunity EN61000 - 4-2 / 4-3 / 4-4 / 4-5 / 4-6
Standards applied for emission ETS300-132-2   CISPR 22 Class B
Efficiency   88 % 90 %
Temperature Storage temperature - 40 deg C to 80 deg C
Permissable ambient - 20 deg C to 50 deg C
Safety   EN60950 / UL1950
Protection   Internal electronic + relays + fuses
Dielectric strength   4000VDC input / output   4000VDC output / earth
2000VDC input / earth
Cooling   Natural
Dimensions
(W x D x H mm)
  438 x 330 x 2U
Weight in Kgs (approx.)   8,5

Sinetech reserves the right to change specifications without prior notice