Sinetech Uninterruptible Power Supplies and Power Protection 19"Rack Mount True Online
Double Conversion
Pure Sinewave
UPS Systems

Home | Products | Email | Contact Details | Profile | Lightning Information
Tel: (++27) 11 886-7874 Fax : (++27) 11 787-0178

Print Version (571kb)
RHC / RHD SERIES 19 " RACK MOUNT
True Online Double Conversion Sinewave
700 / 1000 / 2000 / 3000VA

The RHC / RHD Series is a genuine 19" true online rack mount UPS. Design engineers worldwide agree that the RHC internal configuration is themost effective method of Uninterruptible Power solution in ensuring that the connected load remains completely protected from all types of power related problems. This is because the RHC series is designed to have the inverter continuously pull its power from a completely independent DC source. Whatever the application the RHC system is required to operate in (for instance, providing non-stop conditioned power to sensitive computer and communication equipment in a clean, temperature controlled data centre, or industrial control equipment in a harsh industrial environment), the user is guaranteed that the RHC will always protect the loads connected to it. More than just a robust design, the RHC also allows sophisticated control and monitoring via either the RS-232 port or the interface slot provided. The information collected can then be viewed in a multitude of ways, either over the LAN, WEB or via a SNMP connection.

The RHC Series has an LED display, while the RHD Series has a digital LCD display.

  • Double conversion technology - ensures a fully regenerated sinewave output independent of utility supply
  • Microprocessor controlled - provides instant control and correction for UPS control
  • Auto select input frequency - suitable for use in many different countries
  • 50KHz high frequency operation - allows for a more compact and lighter design
  • RS233/LAN interface and SNMP/http network control - smart communication interfaces for UPS management via a network
  • High efficiency - negligible efficiency trade off for increased output performance
  • Easy access for maintenance - hot swappable battery replacement feature
  • Cold start and generator compatible - suitable for applications in poor power environments
  • Self diagnostics - increases reliability and informs the user of any operating problems
  • Space saving design - Only 2U in height requiring less valuable rack space

RHC UPS

TECHNICAL SPECIFICATIONS

MODEL LED DISPLAY RHC7000 RHC1000 RHC2000 RHC3000
LCD DISPLAY RHD7000 RHD1000 RHD2000 RHD3000
Output VA Rating 700VA 1000VA 2000VA 3000VA
Wattage (100-120V/220-24V) 450W 700W 1400W 2000W
Current (100-120V/220-240V)max. 3A 4.3A 8.7A 13A
Voltage 220, 230, 240V ± 2%
Frequency 50 / 60 Hz Auto select
Wave form Pure sinewave
Harmonic Distortion Less than 3% at full load (Linear load)
Input Voltage 80 V - 145V / 160 V - 275 v
Frequency 45 - 65 Hz Auto select
Runtime Full Load 5 - 7 min. 4 - 5 min.
Half Load 15 min. 12 min.
Transfer Time INV to Bypass / Bypass to INV Less than 4 msec. (2 msec. Min) / Zero-Cross Transfer
Power Failure Recovery 0 msec. to or from battery
Battery DC Voltage 24 VDC 36 VDC 72 VDC 96 VDC
Type 12V / 7AH Lead acid maintenance free 12V / 4.5AH Lead acid maintenance free
Recharge Time 5 - 8 hours
Recharge Current 1.5 A (max.)
Efficiency AC to AC 85% min.
Audible Noise At one meter < 45 dBA < 50 dBA
Indicators LED or LCD Display LINE, INV, BAT, BYPASS, FAULT, BAT / LOAD LEVEL
Auto Restart   Yes
DC Start-up   Yes
Protection Overload 110% of full load with 15 - 20 sec. Delay, 150% immediately
Over / Undervoltage at I/P. O/P Inverter shutdown protection
Phone Jack RJ-11/RJ-45
Short Circuit Shut down and won't transfer to bypass output, will work normally again when short circuit is removed
Approved EMC/LVD (230 V, 50 Hz) EN50091-2 / EN50091-1
Safety TUV GS Mark EN50091-1-1, UL 1778
USA FCC (120 V, 60 Hz) FCC PART 15
CNS BCIQ (110 V, 60 Hz) CNS 13438
IMMUNITY (120V / 110V / 100V,50/60 Hz) IEEE 587 CLASSA
Computer Interface LAN / RS232 Interface Mains fail, battery low & remote shutdown UPS/RS232 communication
Mechanical Dimensions (W x H x D) (mm) 435 X 88 X 463 (19" x 2U) 422 X 132 X 542 (19" x 3U)
Net/Gross Weight (kg) 15.5/18.6 18.4/21.5 32.4/35.7 36.4/39.8
Environment Temperature 0 deg C to 40 deg C
Humidity 0 - 95% Non-Condensing

Sinetech reserves the right to change specifications without prior notice


Home | Full Product List | EMail | Our Contact Details