The unit is of the full wave thyristor regulator type and has the advantage of rugged simplicity and high reliability with low heat dissipation. Protection is provided by electronic current limiting and fuses. An important feature of this unit is parallel operation. This means high current capability and parallel redundant reliability.
The battery chargers are also available in a 19" rack version up to 1 200 watts; or on an open chassis; or built into standard steel cabinets (see picture).
Many standard options are available regarding voltage and current ratings, metering, alarms, smoothing and parallel operation. Three phase units are generally preferred above 3 KW. Other voltages and currents available on request.
DC Output Metering Indications Dimensions Dimensions
Home | Full Product List | EMail | Our Contact Details
Copyright © 2005 Sinetech c.c. All rights reserved.
Print Version (69kb)
PS-4 SERIES
Solid State Thyristor Controlled350W - 25KW
The PS-4 unit is a robust general purpose DC battery charger designed to provide a smooth regulated DC output despite large mains and load variations.

Made in South Africa![]()
Single Phase Units up to 3000 W
Three Phase Units 3 KW - 25 KW
Output Volts
Output Current
Output Volts
Output Current
12 V
10 A / 20 A / 30 A
24 V
60 A / 80 A / 100 A / 200 A / 300 A / 1000 A
15 V
10 A / 20 A / 30 A
48 V
100 A / 200 A / 300 A / 500 A
24 V
10 A / 15 A / 20 A / 30 A / 40 A / 50 A / 60 A / 80 A
48 V
20 A / 30 A / 50 A / 60 A / 70 A
AC Supply
Single Phase 220 V / 230 V (110 V)
Three Phase 380 V / (525 V) Star / 4 Wire + Earth
Supply Variation
±
10% Standard (±
15%) (±
20%) optional
Frequency
50 Hz ±
5 Hz (60 Hz) ±
6 Hz
Regulation
±
1%
Voltage Ripple
General purpose 5% Standard (2%, 1%) optional
Communications
2mV Phosphometric referred 800Hz ( Optional )
Protection
AC Input Fuse or CB
High Speed Thyristor Fuse
Electronic Current Limiting : Yes
Surge Protection : Capacitors and MOV
Loss of Feedback Shutdown : Optional
DC Volts and DC Amps (Standard) Meter 72 x 72 mm Analog ( Digital Metering available on request)
DC Power on LED
Optional Extras
DC under voltage alarm
DC over voltage alarm
Parallel operation
Front panel test points & selector switch (AAC)
Module fail alarm/ parallel operation
DC Circuit Breaker
Digital Meters
Heavy Duty DC Contactor for Undervoltage load disconnect
Size 19" 5U Rack
Standard 19" 5U rack mounted unit, up to 1200 W
483 W x 222 H x 375 D (mm) to 24 V 20 A
483 W x 222 H x 450 D (mm) to 24 V 30 A
483 W x 222 H x 550 D (mm) to 24 V 40 A
Size Standard Cabinet
Standard free standing or wall mounted Cabinets
600 W x 760 H x 325 D (mm) to 48 V 40 A
600 W x 1000 H x 325 D (mm) to 48 V 70 A ( Dimensions for larger units on request)
![]()